Schneider Altivar 12

Specification

1-phase supply voltage: 100…120 V 50/60 Hz
For 3-phase Output 200/240 V motors
MotorLine supply (input)Drive (output)Reference
Power indicated on plate
on plate (1)
Maximum line currentApparent powerPower dissipated at nominal current (1)Nominal current In Max. transient current for
at 100 Vat 120 V60 s2 s
kWHPAAkVAWAAA
0.180.25651181.42.12.3ATV12H018F1
0.370.511.49.31.9292.43.64ATV12H037F1
0.75118.915.73.3484.26.36.9ATV12H075F1
1-phase supply voltage: 200…240 V 50/60 Hz
For 3-phase Output 200/240 V motors
MotorLine supply (input)Drive (output)Reference
Power indicated on plateMaximum line currentApparent powerPower dissipated at nominal current (1)Nominal current In Max. transient current for
at 200 V at 240 V 60 s2 s
kWHPAAkVAWAAA
0.180.253.42.81.2181.42.12.3ATV12H018M2
0.370.55.94.92272.43.64ATV12H037M2
0.550.7586.72.8343.55.35.8ATV12H055M2
0.75110.28.53.5444.26.36.9ATV12H075M2
1.5217.814.96.2727.511.212.4ATV12HU15M2
2.232420.28.493101516.5ATV12HU22M2
3-phase supply voltage: 200…240 V 50/60 Hz
For 3-phase Output 200/240 V motors
MotorLine supply (input)Drive (output)Reference
Power indicated on plateMaximum line currentApparent powerPower dissipated at nominal current (1)Nominal current In Max. transient current for
at 200 Vat 240 V60 s2 s
kWHPAAkVAWAAA
0.180.2521.70.7161.42.12.3ATV12H018M3
0.370.53.631.2242.43.64ATV12H037M3
0.7516.35.32.2414.26.36.9ATV12H075M3
1.5211.19.33.9737.511.212.4ATV12HU15M3
2.2314.912.55.285101516.5ATV12HU22M3
341915.96.69412.218.320.1ATV12HU30M3
45.523.819.98.312816.72527.6ATV12HU40M3